Machine Room Commissioning, Start-up Sequence, Acceptance Checklist & Operation Log

Machine room commissioning is the final verification of the whole refrigeration system after installation, before formal handover. Standard start-up sequence: visual inspection → leak test → vacuum → refrigerant charging → oil check → single component test → load running. Leak test: pressurize with dry nitrogen, hold pressure and detect leak; vacuum target below 500 microns for POE oil system. Charging: charge liquid refrigerant into receiver side; never charge liquid directly into compressor suction port. Commissioning key parameters: superheat, subcooling, condensing pressure, suction pressure, oil level, defrost termination temperature. Xiteliduo provides commissioning checklist, operation manual and alarm troubleshooting document together with equipment. Acceptance items: temperature stability, pull-down time, running current, noise, vibration, all alarm function test. Operation log record: daily room temperature, pressure, ambient temperature, running hour, alarm event and maintenance action. Training for end user: normal operation, alarm judgment, forbidden operation, safe pump down procedure and refrigerant handling. Handover standard: all test data recorded, drawings updated as-built, spare parts list submitted. Refrigeration maintenance & repair company recommends 72 hours continuous load running test before final acceptance.

FAQ

  1. What is the correct order before refrigerant charging? Pressure leak test and vacuum pumping.
  2. What is the vacuum target for POE oil system? Below 500 microns.
  3. Where to charge liquid refrigerant? Receiver side.
  4. What core parameters need recording during commissioning? Superheat, subcooling, suction and condensing pressure.
  5. How long is the suggested continuous load test? 72 hours.
  6. What log content should be recorded daily? Temperature, pressure, running hours and alarms.
  7. What must be tested before acceptance? All protection and alarm functions.
  8. What document should be handed over to customer? As-built drawing, manual, checklist and spare part list.
Siti web artikel ini: https://id.xtldcool.com/news/835.html

Dapatkan rencana penyesuaian produk secara online

Silakan isi persyaratan yang tertera di kotak di bawah ini, dan Anda akan bisa mendapatkannya secara gratis.

Consulting Hotline

+86-18157593311

Xiteliduo & Chuanli

Pabrik asal Tiongkok yang memproduksi Kompresor Piston Semi-Hermetik R32 dan Sistem Pendinginan Industri Turnkey Sesuai Pesanan. Kompresor hasil pengembangan sendiri + solusi pendinginan lengkap, dengan kinerja yang stabil untuk kondisi kerja di iklim tropis maupun suhu sangat rendah.

hubungkan kami

Layanan Teknis: +86-575-83665888;83068555 
Saluran Darurat Kompresor: +86-18157593311 
Saluran Darurat Tabung Pemanas Listrik: +86-13857577938 
Email: helen xiteliduo@163.com 
Pabrik Tabung Pemanas Listrik: No. 150, Desa Donghu, Kota Ganlin, Kota Shengzhou, Kota Shaoxing 
Pabrik Kompresor: No. 679, Kawasan Pengembangan Ekonomi Dongguo, Kota Shengzhou, Kota Shaoxing

Hak Cipta © 2026 Zhejiang Xitelidu Environmental Technology Co., Ltd. & Shengchuanli Environmental Technology Co., Ltd. Semua Hak Dilindungi Undang-Undang.